Skip Navigation Links
Skip navigation links
About EDDL
Technical Resources
Device Management
Standards Groups
About FDI
中文
日本
Skip navigation links
About EDDL
Basics
Supporting Organizations
News Archives
Contacts
Literature
Technical Resources
The Standard
Developer Corner
Training
Articles
Videos
Technical White Papers
Presentations
User Forum
EDDL/DD File Download
Device Management
Device Revision Management
Calibration Trim
Device Diagnostics
Internal Variables
Setup/Configuration
NE107
Standards Groups
About FDI
中文
日本
NE107 

NAMUR NE 107 status signals icons dashboard style

Process variables and manipulated variables are the most important pieces of information from the devices. NAMUR has identified that the status of the devices themselves is also important to help the plant operators run the plant better. This requirement is captured in their NE107 recommendation.

NE107 recommends that operators need a view of the process including the status of the instrumentation in a simple and uniform way regardless of source device.

The NE107 recommendation defines that detailed device-specific diagnostics are summarized as four simple status signals. These signals ensure that the plant operator is not inundated with device troubleshooting details and cryptic error codes. The NAMUR NE107 recommendation harmonizes the display of status for devices.

Intelligent Device Management (IDM) software based on EDDL make use of NE107 for device diagnostic alarm filtering and dashboard displays etc.

Technical White Papers

Tutorial: NAMUR NE107    

Device Diagnostics Deployment and Adoption Guide  

Fieldbus diagnostics: Latest advancements optimize plant asset management  

Articles

A Complete Turnaround (Control Engineering Asia, April 2013)

Presentations

Requirements regarding self-monitoring and diagnosis in field instrumentation

What is NAMUR?

NAMUR is the international user association of automation technology in process industries 
What is NE107?

NE 107 is a recommendation from the NAMUR organization for “Self-Monitoring and Diagnosis of Field Devices” explaining how to make use of diagnostics in intelligent devices

Why display device diagnostics to the operators?

The status of the devices is useful and can help the plant operator to take action as required on the process the device is controlling. See also ISA 18.2 clause 3.1.46

What is a ‘status signal’?

A status signal summarizes the health of the device based on device self-diagnostics and is displayed as one of four categories:
• Failure
• Out of Specification
• Maintenance Required
• Function Check

How each diagnostic maps to which category can be configured in the device. Learn more from the NE107 tutorial and the Device Diagnostics Deployment and Adoption Guide

Will device diagnostics distract the operators?

No. The plant operator is only displayed the simple status signal in order to not be inundated in troubleshooting details.

Where is NE107 implemented?

NE107 is implemented in control systems, Intelligent Device Management (IDM) software part of Asset Management Systems (AMS), and in devices as well as in the EDDL files that integrate these systems and devices. Make sure systems and devices have been tested and registered to support NE107

What action does an operator take on status signals?

The action the operator might take, besides informing a specialist, might include switching the affected loop to manual mode, or send somebody to the field to operate valve by hand.

What do the NE107 status signals look like and what do they mean?

 

 Status Singal

Category 

 Description

 NAMUR NE107 fail status signal

Failed Signal invalid due to malfunction in the device, sensor, or actuator
 NAMUR NE107 out of specification status signal Out of Specification Permissible ambient or process conditions exceeded or the measuring uncertainty of sensors or deviations from the set value in actuators is probably greater than expected
 NAMUR NE107 maintenance required status signal Maintenance Required Advisory: although the signal is valid, the remaining life is nearly exhausted or a function will soon be restricted due to operational conditions e.g. aging of a pH-electrode.
 NAMUR NE107 check function status signal Check Function Signal temporarily invalid (e.g. frozen) due to on-going work on the device.